Peek-Frank: central claims
Source: F. W. Peek Jr., Dielectric Phenomena in High Voltage Engineering, 2nd ed., McGraw-Hill, 1920 (one PDF, 325 pages). Peek worked for General Electric, which had a commercial interest in transmission equipment.
Source gap note. The text is OCR on 324 of 325 pages; equations and tables are often garbled, so the load-bearing pages were read from page images. After QE, deep reads cover Chapters III-V (PDF pp.60-189), the end of VI and VII (pp.196-227), VIII-IX (pp.227-251) and the appendices (pp.277-311), including the corona-loss data appendix, transcribed. Still digest only: front matter and Chapters I-II (pp.1-59), the oil material of Chapter VI on pp.189-195, the design cases of Chapter X (pp.252-276) and the index. The loss law's constant is printed A = 241 on p.237 and 244 on p.242; the fit chain gives 241 (20,500/85). The primary papers Peek cites for the energy-limited-breakdown figures (Hayden and Steinmetz, A.I.E.E. 1910) and the 100,000-cycle loss check (Alexanderson) were not read, so those two items rest on Peek's account of them. Nothing here rests on [memory] alone.
-
Peek's law of visual corona. The surface gradient at which a wire starts to glow rises as the wire gets thinner, g_v = g_o(1 + 0.301/sqrt(r)) kV/cm peak with g_o about 30 kV/cm, and in general g_v = g_odelta(1 + 0.301/sqrt(delta*r)) for relative air density delta, independent of spacing, conductor material and humidity. The constants are group-averaged fits (the "Sigma-Delta" method, with 9 of 19 points discarded), with variants 31(1+0.308/sqrt r) for cylinders and 27.2(1+0.54/sqrt R) for spheres.
-
The energy-storage distance. Air has a constant strength g_o, but rupture needs a finite energy, so the gradient must stay at or above g_o over a distance 0.301*sqrt(r) cm from the wire; Peek attributes this to ionization by collision (electrons chiefly) but states that the form of the rupturing energy "has not been considered", and does not derive 0.301 or the square-root form from ion physics.
-
Empirical corona-loss law for transmission lines. Loss above the disruptive voltage e_o is p = (244/delta)(f+25)sqrt(r/s)(e-e_o)^2 x 10^-5 kW/km, e_o = 21.1 m_o r delta ln(s/r) kV, with irregularity factors, a storm rule e_o x 0.8, and altitude and weather rules. A worked 100-mile line (e_o = 52.0 kV) recomputes correctly, and the book compares calculated with measured losses on the Leadville line and the Au Sable line (15 kW/mile calculated vs 15-20 measured, "preliminary rough measurements"). Corona is expected to be an economic rather than a physical limit on line voltage. The law was fitted by Peek's group-averaging method to single-phase test lines (stated on p.20 and p.286: Line A and Line B are single-phase); the constant is the product of an indoor frequency fit (f+25) and an outdoor 12-test fit, and the deep reader's refits show the outdoor data do not themselves fix the -25. The one out-of-sample check in the book is Alexanderson's 100,000-cycle measurement on two parallel wires (about five points, a GE test; Peek: 'a good check', 'complete conclusions cannot be drawn from this small amount of data'), which supports the frequency scaling of the slope but not the onset voltage.
-
Strength of air at small gaps, and in thin films. Where the gap is shorter than the energy distance the gradient needed for breakdown is far above 30 kV/cm (196 kV/cm at 0.0025 cm for a free sphere gap; sphere-gap average 27.23(1+0.54/sqrt(deltaR))), and entrapped air films in solid insulation break down at the gradient of a free gap of the same thickness (161 kV/cm at 0.0025 cm). The appendix gives a Paschen table (minimum about 350 V at px = 0.05 cm Hg cm).
-
Time lag: impulse voltages break insulation at far higher voltage than 60 cycles. Rupture requires a minimum energy and hence a minimum time ("dielectric spark lag"). In Peek's 1915 half-sine impulse tests (55 to 900 kc) needle-gap impulse ratios run from 1.00 to 2.34, oil and solids 2-3.3, rising further at low air density (up to 5.8), while sphere gaps stay within about 5 percent (so serve as impulse voltmeters), and rain lowers 60-cycle insulator flashover 36-40 percent but impulse flashover only 2-3 percent. The minimum-energy idea also has a measured form in the book: Hayden and Steinmetz (A.I.E.E. 1910, GE) found that gaps set to 30 kV at 60 cycles do not spark over at a 100 kV transient unless the circuit supplies 0.45 J (1.5 A) in air or 1.04 J (4 A) in oil, and Peek states that the disruptive energy of oil is about 30 times that of air. These are circuit energies from another investigation, not an energy stored in Peek's 0.301*sqrt(r) zone, and the figures plot current, not time.
-
D.c. versus a.c. In air and oil, direct-current breakdown equals the a.c. peak (1.41 x the a.c. effective value), with exceptions in the book's own tables (thin wires in cylinders, long needle gaps; Whitehead's compiled positive d.c. corona 4-6 percent lower). In solid insulation (varnished cambric) d.c. strength is 1.27 to 2.59 times the a.c. peak, rising with thickness and time, which Peek ascribes to a.c. dielectric heating.